Environment
GENERAL CHARACTERISTICS
| Electrical Specifications | |
|---|---|
| Nominal Voltage: | 415 V – 50 Hz |
| Capacity Tolerance: | -5%, +5% |
| Connection Type: | Three-phase |
| Power Loss | < 2.5 W/kVAr |
| Maximum Allowable Current (with thermal protection included) | 1.43 In |
| Maximum Allowable Voltage | 1.1 x Un, 8h every 24h |
| Isolation Voltage | 690 V |
| Nominal Impulse Withstand Voltage (Uimp) | 8 kV |
| Box | |
|---|---|
| Degree of protection | IP42 |
| Color | RAL 7035 |
| Degree of Mechanical Resistance | IK10 |
| Head Protection | |
|---|---|
| With Main Switch | Rotary Handle Switch-Disconnector The compensation bank must be protected upstream by a circuit breaker |
| With Circuit Breaker | Molded case circuit breaker Rotary handle on demand |
| Components | |
|---|---|
| Type of Capacitors | VARCap® 480 V – 50 Hz Maximum Overload: Up to 2.0 In Maximum Inrush Current: ≤500 In Operational Ambient Temperature: -40°C – +60°C Overvoltage Protection for all 3 Phases Discharge Resistance 50 V – 1 min |
| Signaling |
|---|
| 3 LED voltage presence indicators on the front panel |