Technical characteristics
| General features | |
|---|---|
| Power (kVA) | Power range from 1 kVA to 3,200 kVA |
| Technology | Thyristor Technology, fast voltage regulation, maintenance-free design |
| Thyristor Configuration |
|
| Inputs | |
|---|---|
| Nominal input voltage | Three-phase model: 400V AC three-phase + Neutral + Ground Model single-phase: 230V AC single-phase + Neutral + Ground (Different voltages are available as an option) |
| Voltage tolerance | Model XS : -15%, +15% Model S : -25%,+15% Model M : -35%,+15% Model L : -50%, +15% |
| Frequency | 50Hz. +/-5% (60Hz. in option) |
| Outputs | |
|---|---|
| Nominal input voltage | Three-phase model: 400V AC three-phase + Neutral + Ground Model single-phase: 230V AC single-phase + Neutral + Ground (Different voltages are available as an option) |
| Voltage tolerance | Between +/-1% and +/-5% (in option) |
| Frequency | 50Hz. +/-5% |
| Overload capacity | 125% 1min. 150% 10sec. 151% and above for 0.2sec |
| Response time | 20msec |
| Correction time | 100msec. – 200msec |
| Efficiency | >97% typical |
| Management, control, and communication interfaces | |
|---|---|
| Control panel with LCD display | LCD display 4×20 and schematic diagram Input voltage, output voltage, load percentage, frequency, information and error status, installation parameters |
| Control panel screen | 7″ touchscreen Input voltage, output voltage, load percentage, frequency, information and error status, installation parameters |
| Remote management interface (optional) | Remote management via web browser with Ethernet connection (optional) Modbus RTU with RS485 connection (optional) |
| Management, control, and communication interfaces | |
|---|---|
| Voltage protection | Electronic protection for low voltage and high voltage |
| Current protection | Input circuit breaker (output circuit breaker on request) |
| Overload protection | Electronic overload protection (1min. at 125% overload, 10sec. at 150% overload, 0.2sec. at >151% overload >151%) |
| Overheating protection | Electronic protection against overheating (the fan starts at 50°C. The load power is cut off at 80°C). |
| Surge arrester | Surge protector Class-I or Class-II (optional) |
| Environmental conditions | |
|---|---|
| Operating temperature | -10°C ~+50°C |
| Operating altitude | 1.500m |
| Humidity | 90% non-condensing |
| Acoustic noise | <55dB (at a distance of one meter with closed door) |
| Cabinet features | |
|---|---|
| Type – Protection class | Free-standing modular cabinet, interior IP21 type (Protection class: IP54 and above. Types of outdoor cabinets are optional) |
| Paint – Color | Epoxy-Polyester powder coating – RAL 7035 |
| Cooling | Forced air cooling with fan controlled by thermostat |